Output Thrust, Stroke Time, Stroke Length, and Weight (all models)
Thrust (lbs.) | Timing | Stroke Length (inches) | Weight 120 VAC | Weight 240 VAC |
1,000 | 4.2 | 5″ to 8″ | 75 | 84 |
1,000 | 4.2 | 7″ to 12″ | 77 | 86 |
1,000 | 4.2 | 11″ to 18″ | 80 | 89 |
Maximum Current (Amps) by Supply Voltage
Voltage (Vac) | |||||||
Maximum Power (W) | 120 | 208 | 240 | 380 | 415 | 480 | 575 |
144 | 1.2 | 0.69 | 0.60 | 0.38 | 0.35 | 0.30 | 0.25 |
Additional Specifications
Operating Conditions | –40° to 85° C. (–40° to 185° F.) 0 to 99% relative humidity |
Communications Interface | HART© protocol and local pushbutton/LED panel and RS-232 serial commands |
Demand Input Signal Range |
4–20 mA, 1–5 V dc |
Minimum Step | 0.1° of span |
Hysteresis | 0.25% of span at any point |
Demand Input Signal Characterization |
Linear: Drive output shaft moves proportionally to the input signal. Square: Drive output shaft moves proportionally to the square of the input signal. Custom: 20 segment configurable curve fit |
Position Feedback Signal | 4–20 mA |
Isolation | Demand input and position Feedback signals are isolated from ground and the ac power line. Signal buffering provides 24 V dc isolation between the Demand and Feedback signals. |
Action on Loss of Power | Output shaft stays in last position |
Action on Loss of Input Signal (Power on) | Stay in place or runs to any preset position (configurable) |
Over-thrust Protection | If the output thrust of the drive exceeds 150% of the drive rating, the motor will shut off (feature can be enabled / disabled). |
Stall Protection | If the motor tries to run in one direction for more than 300 seconds (configurable from 30 to 300 seconds), the motor will shut off. |
Over-travel Protection Switches | Two Form C (Retract and Extend) provide over-travel protection |
Auxiliary Switches (Field Adjustable) |
Two Form C, rated for 1 A, 250 V ac |
Handswitch | Permits local electrical operation, independent of Demand input signal. |
Handwheel | Provides manual operation without electrical power. |
Motor | 120 Vac, single-phase, no burnout, noncoasting. Capable of 60 starts per minute |
Enclosure | Precision-machined aluminum alloy castings, painted with corrosion-resistant polyurethane paint, to provide a rugged, dust-tight, weatherproof enclosure designed to meet NEMA 4X standards. |
Mounting Orientation | Can be mounted in any orientation |